8 Output Networked Power Distribution Mod-Fused
BRAND
Altronix
MFG #
LINQ8PD
SES #
ALT LINQ8PD
UPC
782239953714
Your Price
Usually ships between 3-7 business days
Altronix LINQ8PD network power distribution module facilitates monitoring, reporting and control of one (1) or two (2) low voltage AC or supervised DC power supply/chargers over the network. Reports diagnostics via Email notifications greatly reducing system downtime and eliminating unnecessary service calls. LINQ8PD retrofits with most currently installed multi-output power supply/chargers.
- Input Power
- Input1/Input2: 12VAC-28VAC @ 12.5A each or 12VDC/28VDC @ 12.5A each.
- Note: Do connect AC and DC simultaneously to INP1 and INP2.
- Outputs
- Eight (8) fused outputs rated 3A.
- Power output(s) can be locally or remotely controlled.
- Surge Suppression.
- Status Monitoring
- Power Supply(ies) output voltage and load.
- Voltage and load of each output.
- FACP trigger and reset status.
- Unit temperature (Celsius).
- Power Supply AC and Battery status.
- Battery health.
- Programming Features
- Power Supply(ies) voltage and load limits (High/Low).
- FACP trigger type (wet or dry-N.O./N.C.).
- Input Function (FACP reset/tamper).
- Output Reset Trigger (N.O./N.C.).
- Battery Monitor Configuration:
- Capacity
- Charge Level
- Max. Charge and Discharge Current
- Service Date.
- Configurable Output Relay(s).
- Individual Output Configuration:
- Device ID
- Voltage and Current Limits (High/Low)
- FACP Trigger Setting (latching/non-latching/inactive)
- Battery Backup.
- Network Security
- Secure Socket Layer (SSL).
- Reporting
- E-mail notifications.
- Event Log tracks history.
- Fire Alarm Interface
- Supervised FACP disconnect (Latching or Non-Latching).
- FACP reset (N.C. or N.O.).
- Environmental
- Operating temperature: - 20° to 49° C ( - 4° to 120.2° F).