LCD REMOTE ANNUN RED COMMON INDICATORS - K-RLCDR

BRAND
Kidde
SES #
FWX KRLCDR
MFG #
K-RLCD-R
UPC
793016050793

Your Price

Usually ships between 3-7 business days

Kidde R-Series Annunciators are high-performance remote annunciators that provide status indication and common controls for compatible fire alarm control panels. This family of annunciators offers LCD or LED annunciation. Models are available with and without common controls.

There are three R-Series annunciator models, plus an LED-based expander. Up to two expanders can be connected to any annunciator. The expander includes 24 pairs of LEDs that extend the capabilities of any of the annunciators.

All annunciator models include status LEDs and an internal buzzer. Two models have an LCD text display, and one has 16 pairs of LEDs for zone annunciation. LCD models feature a large back-lit, four by twenty character per line, super-twist liquid crystal display.

R-Series annunciators and expanders are mounted on a standard 4-inch square electrical box, using the included mounting ring. They can also be surface mounted in locking steel enclosures. Three different enclosures are available.

A keyswitch and graphic annunciator interface is available for R-Series annunciator applications. The keyswitch enables or disables common controls. The graphic annunicator interface cards supports 32 LEDs and 16 switches on the graphic panel display.

Graphic Annunicator Interface

The GCI Graphic Annunicator is an interface card that connects the fire alarm control panel to the display panel of an LED-based graphic annunciator. The annunciator card supports 32 LEDs and 16 switches on the graphic panel display. It includes status LEDs and an internal buzzer. The graphic interface is supplied with snap track mounting. It is attached to a plastic mounting rail that requires two EIA panels. The annunciator communicates with the FACP on the RS‑485 data riser. This can be configured for Class A or Class B communication. The annunciator does not provide ground fault isolation. It is a stand-alone unit that can be powered by the FACP or by an approved power supply.

  • LCD models feature large 4 x 20 character backlit LCD display
  • LED models provide 16 pairs of LEDs for zone annunciation
  • Available expander extends capability with 24 pairs of LEDs
  • Up to two expanders may be wired to each annunciator
  • Status LEDs and internal buzzer standard on all models
  • Common controls available for LED and LCD display models
  • Available keyswitch for disabling common controls
  • Standard 4-inch square electrical box mounting
  • Class B or Class A RS485 wiring standard
  • One-, two-, and three-position enclosures available
  • Graphic Annunciator interface, includes common control, indicators and 32 LEDS
  • No programing required, set the address and unit recieves all information from panel
Operating voltage
24V DC, continuous
Standby current
98 mA
Alarm current
113 mA
RS-485 communications
Class A or Class B, 9600 baud
Data wiring
18 to 14 AWG (1.0 to 2.5 sq mm) twisted pair (6 twists per foot minimum). Maximum wire run is 4,000 ft. (1,219 m))
Remote key switch circuit
5V DC at 1 mA, power-limited, unsupervised
Power wiring
18 to 14 AWG (1.0 to 2.5 sq mm)
Display area
4 lines of 20 characters each
Dimensions (H x W x D)
5 5/8 x 8 1/2 x 1 1/2 in. (14.3 x 1.4 x 3.8 cm)
Mounting
North American 4 inch square electrical box or listed enclosure
Temperature
32 to 120F (0 to 49C)
Humidity
0 to 93% RH, noncondensing at 90F (32C)