1270PT ADDRESSABLE FIRE PANEL

BRAND
Potter
SES #
POT AFC1000
MFG #
3992754
UPC
785192024828

Your Price

Usually ships between 3-7 business days

The AFC-1000 is an expandable analog/addressable releasing fire alarm system with a total system capacity of 1270 addresses. Additional capacity on the system is achieved using multi-point SLC modules The control panel utilizes the exclusive Potter protocol that includes a complete line of sensors and modules. The system is expandable with a total of nine additional addressable Signaling Line Circuits (SLC) each with a maximum of 127 devices. Each SLC may be comprised of any combination of smoke sensor, heat detectors or modules and allows for a total of 50 ohms of impedance and may use any wire compliant with the National Electrical Code (NEC).

The AFC-1000 has a 10 Amp power supply with six Notification Appliance Circuits (NACs) and four Input/Output (I/O) circuits. The NACs are rated at 3 Amps each and the I/Os are rated at 1 Amp each. Each output is regulated and power limited. In addition, each output is uniquely programmable and may be configured for steady signal, strobe synchronization, constant power, door holder power, or releasing. The strobe synchronization includes Gentex, AMSECO, System Sensor and Cooper/Wheelock and with the exclusive Quadrasync each output may have a unique brand and all strobes will flash together. The I/Os are designed for inputs such as manual release stations and abort switches that will not require polling and react nearly instantaneously.

The NACs may be expanded using the PSN-1000 series intelligent power supplies. Each PSN-1000 adds another 10 Amps of power, 2 additional input circuits and the AFC-1000 will support up to 31 power supplies. The system will synchronize the strobes system wide. In addition, the PSN-1000E has space to allow the installation of up to six PAD100-SLCE SLC loop expansion cards. The cards mount on a stacker bracket that allows access to all SLC circuit connections.

  • 1,270 addresses available on this analog addressable system
  • Additional system capacity achieved via multi-point SLC modules
  • 1500 software zones
  • NFPA 72 Compliant Smoke Sensitivity Test Built-In
  • System Operates as Class A or Class B for SLC, P-Link and NACs
  • 10 Amp Power Supply, Expandable to 315 amps
  • 6 NACS, Regulated, Rated at 3 Amps each, expandable to 192
  • 4 Input/Output (I/O) Circuits for system flexibility rated at 1 Amp each, ideal for manual release and abort
  • Strobe Synchronization and System Wide Sync for Gentex, AMSECO, Cooper Wheelock and System Sensor strobes
  • Dedicated Alarm, Supervisory and Trouble Relays
  • 4,000 Event History Buffer
  • Optional two line DACT with UD-1000 that can report General, Zone or Point Information
  • Built in IP communicator
  • Ethernet Port for Programming and Network Connectivity
  • E-Mail System Status, Reports and Event Information
  • Product includes 5 year warranty
Dimensions
18 15/16"W x 27 5/16"H x 4 7/16"D
AC Mains
5.0 Amps @ 120 VAC 50/60 HZ - 3.0 Amps @ 240 VAC 50/60 HZ
Enclosure
16 gauge cold rolled steel with removable locked door with Lexan viewing window
Battery
Standby Current-130 mA - Alarm Current-200 mA - 10 Amps power for NACs, I/O, and P-Link - 3 Amps per NAC, regulated - 1 Amp per I/O circuit, regulated - Battery Charger range 8-55 Ah - Battery Charger voltage 27.3 VDC - P-Link maximum current of 1 Amp
Temperature and Humidity Range
32° to 120° (0°C to 49°C) with a maximum humidity of 93% non-condensing.