4WIRE PE SMOKE W/HEAT ANDPLUG IN BASE

BRAND
System Sensor
SES #
SYS 4WTB
MFG #
4WT-B
UPC
783863017629

Your Price

Usually ships between 3-7 business days

The 4WT-B is a 4-wire, photoelectric i3 smoke detector with a 135°F fixed thermal sensor.

System Sensor i3 series smoke detectors represent significant advancement in conventional detection. The i3 family is founded on three principles: installation ease, intelligence, and instant inspection. Installation ease. The i3 line redefines installation ease with its plug-in design. This allows an installer to pre-wire bases (included with heads). The large wire entry port and in-line terminals provide ample room for neatly routing the wiring inside the base. The base accommodates a variety of back box mounting methods as well as direct mounting with drywall anchors. To complete the installation, i3 heads plug into the base with a simple Stop-Drop 'N Lock action. Intelligence. i3 detectors offer a number of intelligent features to simplify testing and maintenance. Drift compensation and smoothing algorithms are standard with the i3 line to minimize nuisance alarms. 2-wire i3 detectors can generate a remote LEDindicated maintenance signal when connected to the 2W-MOD2 loop test/maintenance module or a panel equipped with the i3 protocol. The SENS-RDR, a wireless device, displays the sensitivityof i3 detectors in terms of percent-per-foot obscuration. Instant inspection. The i3 series provides wide-angle red and green LED indicators for instant inspection of the detector's condition: normal standby, out-of-sensitivity, alarm, or freeze trouble. When connected to the 2W-MOD2 loop test/maintenance module or a panel with the i3 protocol, the EZ Walk loop test feature is available on 2-wire i3 detectors. This feature verifies the initiating loop wiring by providing LED status indication at each detector.

  • Plug-in detector line, mounting base included
  • Large wire entry port
  • In-line terminals with SEMS screws
  • Mounts to octagonal and single-gang back boxes, 4-square back boxes, or direct to ceiling
  • Stop-Drop 'N Lock attachment to base
  • Removable detector cover and chamber
  • Built-in remote maintenance signaling
  • Drift compensation and smoothing algorithms
  • Simplified sensitivity measurement
  • Wide-angle, dual-color LED indication
  • Loop testing via EZ Walk feature
  • Built-in test switch
Alarm Contact Ratings:
0.5 A @ 30V AC/DC
Alarm Current:
20mA max. @ 12V, 23mA @ 24V
Detection:
Photoelectric
Dimensions:
2.0" (51mm) H x 5.3" (127mm) Dia.
Freeze Trouble:
41°F (5°C)
Heat Sensor:
135°F (57.2°C) fixed
Maximum Ripple Voltage:
30% of nominal (peak to peak)
Operating Humidity Range:
0% to 95% RH, non-condensing
Operating Temperature Range:
32° to 100°F (0° to 37.8°C)
Operating Voltage:
12/24 V non-polarized nominal, 8.5 min. to 35 max.
Sensitivity:
2.5%/ft. nominal
Standby Current:
50 µA max. avg.
Weight:
6.3 oz. (178 g)
Wiring Gauge:
14-22 AWG
Wiring:
4-wire